Front Panel Features
1. TekSecurity RJ-12 connection. Allows for quick connect of TekSecurity without having to make
wiring connections.
2. Occupancy Sensor connection. Includes the 24 Volt power connection to operate the occupancy
sensor.
3. DO: Digital logic Outputs 2 and 3 - 300 ma at 24 volts. These outputs must share a common
ground with the connected device. PU: 24 volt @ 8 ma (2.7K) pull-up resistor. These resistors
may be required to connect to a Digital Output to provide voltage for the connected device.
4. Logic Inputs 4and 3: Use these inputs for sensing an on or off state of device like a security
connection, a room occupancy detector, a power monitor or a control button.
5. Serial connection Port 2: This connection is a programmable RS-232 data port used to pass data
between the TekMonitor and a connected device.
6. The LAN connection is an auto sensing 10/100 Ethernet connection supporting DHCP, TCP/IP,
UDP, SMTP and Telnet. This port also supports Power-Over-Ethernet.
7. 24 volt connection: Use this power connection to power another device like an occupancy sensor
or power the TEK 2 from another power source, like a power pack for an occupancy sensor.
The TEK 2 does not come with an external 24 volt power supply. Power-Over-Ethernet is supported.